| SKU | | | ME-2000-WPTU |
|---|
| WEIGHT | | | 26.0000 |
|---|
| PHYSICAL DIMENSIONS | | | 419 X 190 X 318 (mm) |
|---|
| CAPACITY | | | 2000 VA / 1600 W |
|---|
| VOLTAGE RANGE LOW LINE TRANSFER | | | 160VAC/140VAC/120VAC/110VAC±5% ( based on load percentage 100% – 80 % / 80 % – 70 % / 70 – 60 % / 60 % – 0) |
|---|
| VOLTAGE RANGE LOW LINE COMEBACK | | | 168VAC/148VAC/128VAC/118VAC ± 5 % ( based on load percentage 100% – 80 % / 80 % – 70 % / 70 – 60 % / 60 % – 0) |
|---|
| VOLTAGE RANGE HIGH LINE TRANSFER | | | 300 VAC ± 5 % |
|---|
| VOLTAGE RANGE HIGH LINE COMEBACK | | | 290 VAC ± 5 % |
|---|
| FREQUENCY RANGE | | | 40Hz ~ 70 Hz |
|---|
| PHASE | | | Single phase with ground |
|---|
| POWER FACTOR | | | ? 0.99 @ nominal voltage (input voltage) |
|---|
| OUTPUT VOLTAGE | | | 200/208/220/230/240VAC |
|---|
| AC VOLTAGE REGULATION (BATT. MODE) | | | ±1% (Batt. Mode) |
|---|
| FREQUENCY RANGE (SYNCHRONIZED RANGE) | | | 47 ~ 53 Hz or 57 ~ 63 Hz |
|---|
| FREQUENCY RANGE (BATT. MODE) | | | 50 Hz ± 0.25 Hz or 60Hz ± 0.3 Hz |
|---|
| OVERLOAD | | | 100%~110%:audible warning 110%~130%: UPS shuts down in 60 seconds at battery mode or transfer to bypass when the utility is normal >130%:UPS shuts down immediately at battery mode or transfer to bypass mode when the utility is normal |
|---|
| CURRENT CREST RATIO | | | 3:1 |
|---|
| HARMONIC DISTORTION | | | ? 3 % THD (linear load) ? 6 % THD (non-linear load) |
|---|
| WAVEFORM (BATT. MODE) | | | Pure Sinewave |
|---|
| AC TO DC | | | Zero |
|---|
| INVERTER TO BYPASS | | | 4 ms |
|---|
| AC MODE | | | 90% |
|---|
| BATTERY MODE | | | 87% |
|---|
| BATTERY TYPE | | | 12 V / 9 AH |
|---|
| NUMBERS | | | 6 |
|---|
| RECHARGE TIME | | | 4 hours recover to 90% capacity (Typical) |
|---|
| CHARGING CURRENT | | | 1.0 A (max.) |
|---|
| CHARGING VOLTAGE | | | 82.1 VDC ±1% |
|---|
| BATTERY TYPE & NUMBERS | | | Depending on the capacity of external batteries |
|---|
| CHARGING CURRENT | | | 1.0A/2.0A/4.0A/6.0 A ±10% |
|---|
| CHARGING VOLTAGE | | | 82.1 VDC ±1% |
|---|
| HUMIDITY | | | 20-90 % RH @ 0- 40°C (non-condensing) |
|---|
| NOISE LEVEL | | | Less than 50dBA @ 1 Meter |
|---|
| OPTIONAL USB/RS-232 PORT | | | Supports Windows® 2000/2003/XP/Vista/2008/7, Linux, Unix and MAC |
|---|
| OPTIONAL SNMP | | | Power management from SNMP manager and web browser |
|---|